Effertz automatic fire curtain “Fibreflam® Iso6”
Classification EI60-C5 according to EN 13501-2.
Meeting all safety requirements of product standard EN 13241 for industrial doors.
CE-marking with Declaration of Performance according to EN 16034, EN 13241 and EU Construction Products Regulation (CPR).
Insulating textile fire rolling curtain as follows:
- Insulating curtain made of special high-temperature-resistant fabric and insulating internal strips (European patent granted), which guarantees a good and narrow coiling
- Safety contact strip at the bottom of the curtain, helix cable
- Side-guides made of hot-galvanized steel
- Non-galvanized steel parts are protected by a single coating of primer
- Electrical drive 3/N/PE ~ 400 V 50 Hz as standard. Curtain closing in event of an alarm without electrical power at a controlled speed of approx. 10 – 15 cm/s (self-closing, gravity fail-safe operation)
- Drive chain with a safety factor of 6, below 2,50 m height with chain guard
- Fall arrestor in conformity with EN 12604
- Release device with backup battery to hold open the curtain even in case of failure of main power supply for some time
- Optical smoke detectors
- Siren that is triggered automatically in case of a fire alarm
- 1 key contact switch for surface mounting, prepared for profile half-cylinder
- Self-hold (impulse control) to open, dead man’s control to close