Effertz Fire Stacking Door type Firewall T907 / T925
Classification EI90-C5 according to EN 13501-2 and EN 16034.
Durability of self-closing: 200.000 cycles (C5).
Meeting the applicable safety requirements of door product standard EN 13241.
Declaration of Performance and CE-marking according to EN 13241 and EN 16034.
Thermal insulating fire stacking door:
- Door sections made from lightweight fire protective boards
- Surface: raw surface of the fire boards (may be painted or laminated by customer or by Effertz. The latter at an extra cost)
- High safety standard: Self-monitoring safety contact bar at the bottom of the lowest panel
- Side guides with fire protective cover
- All steel parts galvanized or protected by a single coating of primer
- Electrical drive 3/N/PE 400 VAC 16 A, 50 Hz on right-hand side
- Fall arrestor in accordance with EN 12604 and EN 12453
- Drive chain with a safety factor of 6
- Control unit with integrated hold-open and release device. Integrated backup battery to hold the door open for some time even in case of failure of mains power
- One potential free break contact for remote release by central fire alarm system (CFAS) or external manual release
- In case of fire the roller shutter will close without electrical power at a limited speed of approx. 10 – 15 cm/s, even if the contact to the control box is disconnected (self-closing, gravity fail-safe)
- Compact HMI with integrated UP-DOWN key switch, prepared for profile half-cylinder, and a push button for manual emergency release
- Dead man’s mode (self-hold to open possible for door height > 2,50 m)
- Optical smoke detectors (2 per 4 m width)
- Siren with flasher being triggered in case of a fire alarm (acc. to EN 12604)
- Documentation in English or German in accordance with Effertz documentation standard in electronic form (PDF)